Generac Error Code 2800

Back to Troublshooting

WHAT'S THE PROBLEM?


Select the statement that best describes your problem.
  1. Generac Error Code 2800 Reset
  2. Error Code 2800 On Generac 22 Kw Gen Set
  3. Generac Error Code 2800
DISPLAYED ALARME-CODE BREAKDOWNDESCRIPTIONNOTES
Controller FaultNo E-code on HSBReplace Controller
Overcrank1100Condition - Engine Cranks but will not Start Unit turns over but will not start. Controller is receiving signal on Wire 18.Problem 17
Overspeed1200Prolonged Over 72 Hz for 3 seconds. Possible cause: Stepper motor/mixer body assembly issue.Test 12
Overspeed1205Instantaneous Over 75Hz for .1 second (100 milliseconds). Possible cause: Stepper motor/mixer body assembly issue.Test 12
Low Oil Pressure1300Occurred while running The default Extended alarm for low oilpressure. Check oil level and pressure.Test 61
High Temperature1400Condition - Air Flow Impeded I Flow Issue Check the inleUoutlet for debris.Test 62
RPM Sensor1501Twin Cylinder+Running Twin Cylinder Running faults to RPM sensor loss. Possible Causes: air pocket in fuel line. dirty fuel, missing ignition pulse (loss of one of the primary coils).Test 50 and Test 64
RPM Sensor1505Twin Cylinder+Cranking Twin Cylinder Cranking faults to RPM sensor loss Possible Cause: starter motor issue, missing ignition pulse (loss of one of the primary coils).If engine cranks, Test 64. If engine does not crank, Problem 15.
RPM Sensor1511Single Cylinder+Running Single Cylinder Running with Low Fuel Pressure faults to RPM sensor loss Possible Causes: air pocket in fuel line,dirty fuel.Test 50 and Test 64
RPM Sensor1515Single Cylinder+Cranking Single Cylinder Cranking faults to RPM sensor loss Possible Cause: starter motor issue.If engine cranks, Test 64. If engine does not crank, Problem 15.
Underspeed1600Condition - Unit is Overloaded Unit is Overloaded slowing engine speed, fuel supply low or throttle control problem.Problem 1, Test 50 or Test 12
Overvoltage1800Prolonged Over-VoltageProblem 2
Undervoltage1900Prolonged Under-Voltage Undervoltage due to loss of voltage for some time (10+ seconds).Test 5
Undervoltage1901Instantaneous Undervoltage due to sudden loss of voltage.Problem 1
Undervoltage1902Both Zero Crosses missing Undervoltage due to faulty excitation winding.or zero cross circuit.or circuit in general. Possible cause: loose wiring, field boost hardware failureProblem 1
Undervoltage1906Single Zero Cross missing Undervoltage due to faulty excitation winding , zero cross circuit, or circuit in general. Possible cause: field boost hardware failureProblem 1
Wiring Error2099Customer connection low voltage and high voltage wires are crossed.Check customer connection in generator
Overload Remove Load2100Overloaded - Default (Output Current Method) Unit is overloaded, one of the two CTs is detecting an overload condition. Check transfer switch loadshed functionality. (Change load dynamics or utilize loadshed).Remove Load
Undervoltage Overload2299Unit was overloaded and attempted to start with a large load connected. The unit can not ramp up the generator voltage to its normal target volt- age value if it starts with a large load connectedRemove Load
Stepper Overcurrent2399Current flow in stepper coil(s ) above specificationTest 12
Fuse Problem2400Missing I Damaged Fuse The 7.5 amp Controller Fuse is missing or blown (open).Test 44
Low BatteryCondition-> Battery less than 12.1Volts for 60 secondsTest 45
Battery ProblemCondition-> More than 16 Volts of battery voltage or 600 milliamperes or more of charge current at the end of an 18 hour chargeTest 45
Charger WarningLess than 12.5 volts of battery voltage at the end of a 18 hour chargeProblem 22
Charger Missing ACAC power is missing from the battery charger inputProblem 22
SEEPROM AbuseCondition-> more than 1200 writes to the EEPROM in a 5 minute period.

Generac Error Code 2800 Reset

Generac 24kw error code 2800Generac Error Code 2800

Error Code 2800 On Generac 22 Kw Gen Set

Generac

I'm being flooded with questions about the 2800 shutdown fault code for Air Cooled Generac generators. This code is VERY simple to fix. The new Generac WiFi products that are shipping come standard with the Aux Shutdown kits installed. The 15kW are larger units have 2 switches, while 14kW and lower use just 1 switch.

Generac Error Code 2800

Generac error code 2800
  1. This is a list of the Generac Evolution e-Codes (alarm codes) that you may see on the display. Under each is a brief description of what the problem is and the possible causes. If you need more help, please post a new topic with your particular information so that we can help!
  2. E-CODE BREAKDOWN DESCRIPTION NOTES; Controller Fault: No E-code on HSB: Replace Controller: Overcrank: 1100: Condition - Engine Cranks but will not Start Unit turns over but will not start. Controller is receiving signal on Wire 18. Problem 17: Overspeed: 1200: Prolonged Over 72 Hz for 3 seconds. Possible cause: Stepper motor/mixer body.
  3. Last updated on February 18th, 2021 at 10:03 am. A generator is a very useful device at times of power outages.Sometimes, your generator may face some problems. One of the most common problems that a generator faces is that it starts well, runs for a few seconds, and then shuts down.
  4. Auxiliary shutoff switch tripped or broken.